C150 / C110MC Troubleshooting
Applies to: C150 (6 Zone CPU) · C110MC (Basic CPU)
Zones are not opening or responding
One or more zones are unresponsive to open/close commands.
Steps to resolve:
- Disconnect the zone motor from the problem port and plug it into a different unused port on the CPU
- Verify the CT24ACE transformer is powered and outputting ~24VAC
- Check wiring polarity and that all connectors are fully seated
- On the C110MC, confirm zones are wired starting at Zone 1 consecutively — skipped ports are not supported on the basic CPU
note
On Daikin systems, it can take up to two minutes for dampers to open after a command is sent.
Wall controller not powering on
The C110WC push button controller or any connected screen shows no power.
Steps to resolve:
- Check the Cat5e cable between the CPU and the wall controller — re-seat both ends
- Try a different port on the CPU if multiple ports are available
- Verify the CT24ACE transformer is providing ~24VAC to the CPU
- If the issue persists, the CPU or wall controller may need replacement — contact your installer
No 24VAC supply — system not operating
The system has no power or zones are unresponsive across the board.
Check the following:
- Verify the transformer is plugged into an earthed GPO and the GPO is switched on
- Confirm output voltage from the transformer is ~24VAC
- Ensure the transformer is not wired directly to the AC unit's power supply — this is not supported
- Check wiring polarity and that all connectors are fully seated