CDTS Troubleshooting
Applies to: CDTS (In-Duct Temperature Sensor)
CDTS not showing temperature in the app or on screen
The supply air temperature reading is absent or shows dashes.
Steps to resolve:
- Check the RJ11 cable is seated in the CDTS port on the C225 — not a zone damper port
- Try a different RJ11 cable to rule out a cable fault
- The sensor may take up to 60 seconds after power-on to appear
- Confirm the CDTS is installed upstream of all zone dampers in the supply air duct — if installed downstream of a closed damper it may read ambient temperature incorrectly
CDTS reading seems inaccurate
The supply air temperature reading does not match expected values.
Steps to resolve:
- Confirm the sensor probe is fully inserted into the duct and securely clamped
- Ensure the sensor is positioned upstream of all zone dampers so it measures conditioned air, not return/mixed air
- Allow a few minutes for the reading to stabilise after the AC unit starts