CEXT Troubleshooting
Applies to: CEXT (Zone Extender)
Zones 9–14 not responding
Zones connected to the CEXT zone extender are unresponsive.
Steps to resolve:
- Confirm the CEXT is correctly plugged into the expansion port on the C225 CPU
- Check that zone motors are wired to CEXT ports starting at Zone 9 consecutively
- Verify the CT24ACE transformer is providing ~24VAC — the CEXT is powered through the C225
- In the iZone app, go to Setup → Configure AC and confirm the zone count includes the CEXT zones
CEXT not detected by the C225
The system only shows 8 zones and the CEXT zones are absent.
Steps to resolve:
- Power off the system by disconnecting the CT24ACE transformer
- Re-seat the CEXT firmly onto the C225 expansion connector
- Power the system back on and allow 30 seconds for zone detection
- If still not detected, try a different CEXT unit to rule out a hardware fault