Emerald
Module used to integrate with an Emerald AC unit. The iZone AC unit module (C325H) connects to the CPU module (C225) to enable communication with a ducted AC unit.
Emerald Compatibility
Confirmed compatible with C325H v2.4. Uses the same control method and wiring as Hitachi (TB2: A-B). Works as a Hitachi AC unit for iZone integration.
Current Firmware Version - 2.4
Supported Models
Compatibility
| SERIES & kW | INDOOR | OUTDOOR |
|---|---|---|
| R32 High/Medium Static Ducted 16 kW | ACR160D | ACR160U |
| R32 High/Medium Static Ducted 20 kW | ACV200D | ACV200U |
Notes
Emerald ducted units listed above were manufactured by Hitachi per product owner discussion. Treat selection and wiring as per Hitachi C325H.
Sensor Options
- Can use RA, Zones, Master or RF as the controlling sensor.
- Polarity is not critical on A/B communication pair.
Connection and Wiring
- Connect a shielded, 2-core, twisted pair control cable from the C225 / C325H to the fan coil control terminals TB2: A and B, with earth/shield bonded at the fan coil end.
- Do not apply any voltage to this communication cable.
- Wiring is identical to Hitachi C325H. Refer to: C325H - Hitachi