Emerald Compatibility

Confirmed compatible with C325H v2.4. Uses the same control method and wiring as Hitachi (TB2: A-B). Works as a Hitachi AC unit for iZone integration.

Current Firmware Version - 2.4

Supported Models

Compatibility

SERIES & kWINDOOROUTDOOR
R32 High/Medium Static Ducted 16 kWACR160DACR160U
R32 High/Medium Static Ducted 20 kWACV200DACV200U

Notes

Emerald ducted units listed above were manufactured by Hitachi per product owner discussion. Treat selection and wiring as per Hitachi C325H.

Sensor Options

  • Can use RA, Zones, Master or RF as the controlling sensor.
  • Polarity is not critical on A/B communication pair.

Connection and Wiring

  • Connect a shielded, 2-core, twisted pair control cable from the C225 / C325H to the fan coil control terminals TB2: A and B, with earth/shield bonded at the fan coil end.
  • Do not apply any voltage to this communication cable.